해당법규
건축물 방화구조규칙 제26조
건축자재등 품질인증 관리기준
건축법시행령 제64조
갑종 방화문 을종 방화문에 현재 법규에서는 60분+방화문, 60분방화문, 30분 방화문으로 변경되었다
1방화문
1-1) 방화문의 구분
구분 방화무 성능 기준
60분+ 방화문
연기 및 불꽃을 차단할 수 있는 시간이 60분 이상이고, 열을 차단할 수 있는 시간이 30분 이상
인 방화문
60분 방화문 연기 및 불꽃을 차단할 수 있는 시간이 60분 이상인 방화문
30분 방화문 연기 및 불꽃을 차단할 수 있는 시간이 30분 이상 60분 미만인 방화문
방화문 종류 설치장소 구분
60분방화문, 30분 방화문
특별피난계단,부속실과 계단실사
이문
철재방화문,목재방화문,유리방화
60분 방화문 문,E/V방화문/슬라이딩 방화문
모든방화구획 출입문
방화벽 출입문
특별피난계단 등
60분+방화문 공동주택 대피공간
기타 주의사항
방화문의 유효폭이 900mm이상 확보되어야 하므로, 실제 문 폭은 1,100mm를 적용하여야 유효폭이 확보되는 것
을 명심해야함
일반적인 문 높이는 2,100이상 (유효높이 2m이상)